Product Details:
Payment & Shipping Terms:
|
Model: | KDT-15-5 | Current: | 0-100A |
---|---|---|---|
Busbar Size: | 4/5mm | Certification: | ISO9001 |
Type: | Compact Busbar Plug | Lifespan: | 4 Years |
High Light: | 200A Busbar Socket Copper Pins,100A Busbar Socket Copper Pins,ISO9001 Busbar Copper Contactor |
Compact Busbar Socket Copper Pins Busbar Accessories plug stab fingers
Model | Current | Busbar Size | Type | Remark |
KDT-15-5 | 0-100A | 4/5mm | Compact busbar plug | T Type |
KDT-18-5 | 100-200A | 4/5mm | Compact busbar plug | T Type |
KDT-22-5 | 250-350A | 4/5mm | Compact busbar plug | T Type |
KDT-30-5 | 400-630A | 4/5mm | Compact busbar plug | T Type |
KDT-15-6 | 0~200A | 6mm | Compact busbar plug | T Type |
KDT-18-6 | 250-350A | 6mm | Compact busbar plug | T Type |
KDT-28-6 | 400-630A | 6mm | Compact busbar plug | T Type |
KDF-125 | 0-125A | 19 phase distance, 22 phase distance, 26 phase distance above |
Air busbar plug | F Type |
KDF-160 | 125~160A | Air busbar plug | ||
KDF-250 | 160-250A | Air busbar plug | ||
KDF-630 | 315~630A | Air busbar plug |
Installation Guideline of Tap Off Unit (Plug-In Type)
There are two types of plug-in tap-off units :
1) Plug-in tap-off units without automatic clamping system .
2) Plug-in tap-off units with automatic clamping system.
Step 1: Open or remove the tap-off unit cover.
Step 2: Install the protection device in the tap-off unit.
Step 3: Remove the IP protection on the outlet of the run component.
Step 4: Prepare the output cable glands and connect the cables to the tap-off unit.
Step 5: Check that the protection device is switched off and carefully inspect the tap-off unit for tools and objects that may have been left inside the tap-off unit.
Step 6: Position the rear of the tap-off unit on the run component.
Step 7: Plug the tap-off unit into the run component.
Step8: Lock the tap-off unit on the run component using the locking handle located inside the tap-off unit
Step9: Secure the tap-off unit on the run component using the fixing mechanism.
Step10: Close the tap-off unit cover. The system and the load are ready to be energized.